MEASURED VALUE
Two-state signal
Pulses
BINARY INPUT
Parameters of the voltage contact „L“ level input voltage:< 0,4 V(*);
„H“ level input voltage:> 2 V;
Minimum voltage applicable:0 V;
Maximum voltage applicable:+30 V DC
Parameters of the voltage-free contact Contact resistance in „switched-on“ state:< 10 kOhm;
Contact resistance in the „switched-off“ state:> 300 kOhm;
Contact voltage in the „switched-off“ state: ca 3 V;
Minimum state duration necessary for latching the state:1s
COUNTER INPUT
Counter parameters Range 24 bits (16 777 215), the possibility of letting the counter overflow
Maximum pulse frequency configured for voltage input - max. 5kHz
configured for a voltage-free or open-collector transistor - max. 200Hz
Operating temperature -20 to +60 °C
Channels 4x binary input or 2x binary input a 2x counter
Memory 500,000 values in noncyclic logging mode; 350,000 values in cyclic record mode
Recording interval to the internal memory adjustable from 1 second to 24 hours
Recording interval to the COMET Cloud from 5 minutes
The interval for measuring and evaluating alarms is adjustable 1 s, 10 s, 1 min
Recording mode noncyclic - data logging stops after filling the memory
cyclic - after filling memory oldest data is overwritten by new
Real-time clock year, leap year, month, day, hour, minute, second
Power rechargeable Li-Ion battery A8200, 3.6V/5200mAh
Protection class IP20
Dimensions 61 x 93 x 53 mm, with antenna 120 x 93 x 53 mm
Weight (including batteries) approx. 270 g
Warranty 3 years
La produs nu au fost adăugate aprecieri
Veți fi primul care evaluează produsul.
|