TECHNICAL DATA MEASURED VALUE Two-state signal Pulses BINARY INPUT Parameters of the voltage contact „L“ level input voltage:< 0,4 V(*); „H“ level input voltage:> 2 V; Minimum voltage applicable:0 V; Maximum voltage applicable:+30 V DC Parameters of the voltage-free contact Contact resistance in „switched-on“ state:< 10 kOhm; Contact resistance in the „switched-off“ state:> 300 kOhm; Contact voltage in the „switched-off“ state: ca 3 V; Minimum state duration necessary for latching the state:1s COUNTER INPUT Counter parameters Range 24 bits (16 777 215), the possibility of letting the counter overflow Maximum pulse frequency configured for voltage input - max.